Space saving designed UPS
Voltage | 120 VAC (85 VAC to 155 VAC before going to battery, when configured with batteries) |
---|---|
Frequency | 40 Hz to 70 Hz |
Voltage | 120 VAC ±3% |
---|---|
Frequency | 50 Hz or 60 Hz |
Current | 10.4 A |
Rating | 1250 VA / 875 W |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | 3.00% |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | -40°C to +74°C (-40°F to +165°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Input | IEC-320, C14 male connector |
---|---|
Outputs | IEC-320, C13 female receptacles (2) |
Dimensions H x W x D (in) |
1.7 x 15.25 x 8.5 (1U) |
Weight (lb) | 8 |
Cooling | Low velocity, Forced air |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection |
---|---|
Certifications | FCC Class A, IEEE 587/ANSI C62.4, IEC 555@ 120 VA, NEMA |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
3 to 5 hrs with SP 485B battery pack, 48 to 72 hrs with Outpost or Garrison batteries |
Visual Indicators | Battery status, AC output, AC input, Alarm |
---|---|
Switches / Control Panel | System power, Cold start, Load I, Load II |
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery |
Intelligent Computer Interfaces | 1 each DB9-F (RS232 and signal interface pins) and 1 each USB |
External Battery Pack | SP 48SB battery pack. Compact design. Ideal for runtime requirements less than an hour. |
---|