Built for the most delicate precision instruments
Voltage | 120 VAC +12%, -25% (without battery discharge) |
---|---|
Frequency | 45 Hz to 65 Hz |
Voltage | 120 VAC ±3% |
---|---|
Frequency | Software selectable to sync with input utility or run at crystal controlled 50/60 Hz ±1 Hz |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | 3.00% maximum (linear), 5.00% maximum (non-linear) |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | 0°C to +50°C (+32°F to +122°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Noise Level | 39 dBA to 42 dBA at 5 ft |
Input | NEMA 5-15P plug with 6 ft cord (1250 - 1500 VA connectors), NEMA 5-20P plug on 6 ft cord (2000 - 2400 VA connectors) |
---|---|
Outputs | Duplex hospital grade receptacle 5-15R, 1.25K-1.5K - 5-20R, 2K-2.4K |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, RS232 data interface, Inverter powers load continuously, Continuous operation on -25% to +12% utility without draining batteries, Automatic bypass, AC output (2 channel load control), Rear mounted ground stud |
---|---|
Certifications | FCC Class A, IEEE 587/ANSI C62.4, IEC 555@ 120 VA, CUL, UL 1778, UL-60601-1 |
MTBF | Inverter: > 100,000 hrs |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
8 hrs (more time required with extended battery option) |
Visual Indicators | Battery level, Load level, AC in, Inverter on, Summary alarm, Alarm silence, Load on |
---|---|
Switches / Control Panel | System power, Cold start, Load I, Load II, Test, Alarm silence |
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
Intelligent Computer Interfaces | RS232 data interface (DB-9), Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software), Compatible with Systems Enhancement™ UPS control software |
Contact Closures | DB-9, Open collector, Optional dry contact module |
SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
---|
Model | VA | Watts | Input Current | Output Current | Rating | Backup Time* 100% / 50% Load |
Weight (lb) | Rackmount H x W x D (in) |
---|---|---|---|---|---|---|---|---|
S 1250 | 1250 | 875 | 8.8 A | 10.4 A | 1250 VA / 875 W | 7.0 minutes / 21.0 minutes | 80 | - |
S 1500 | 1500 | 1050 | 10.7 A | 12.5 A | 1500 VA / 1050 W | 5.0 minutes / 17.0 minutes | 80 | - |
S 1500-601 | 1500 | 1050 | 10.7 A | 12.5 A | 1500 VA / 1050 W | 5.0 minutes / 17.0 minutes | 80 | - |
S 2000 | 2000 | 1400 | 14.3 A | 16.7 A | 2000 VA / 1400 W | 5.0 minutes / 18.0 minutes | 100 | - |
S 2400 | 2400 | 1680 | 18.3 A | 20.0 A | 2400 VA / 1680 W | 5.0 minutes / 18.0 minutes | 100 | - |
* Backup time is based on 41 Ah batteries