Globally deployable power protection
Voltage | Selectable ranges (nominal): 120/208, 120/220, 120/230, 120/240 VAC |
---|---|
Frequency | 48 Hz to 62 Hz (nominal) |
Voltage | 120 VAC ±3% (standard), 230 VAC (with optional transformer) |
---|---|
Frequency | 50 Hz or 60 Hz, Software selectable to sync with input utility or run at crystal controlled 50/60 Hz ±1 Hz |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | 3.00% maximum (linear), 5.00% maximum (non-linear) |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | 0°C to +40°C (+32°F to +104°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Noise Level | 39 dBA to 42 dBA at 5 ft |
Input | IEC on unit with 6 ft - NEMA 5-15P (1250 - 1500 VA connectors), IEC on unit with 6 ft - NEMA 5-20P (2000 - 2400 VA connectors) |
---|---|
Outputs | 5-15R receptacles |
Cooling | Low velocity, Forced air |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, Inverter powers load continuously, Continuous operation on -25% to +12% utility without draining batteries, Automatic bypass, AC output (2 channel load control), Rear mounted ground stud |
---|---|
Certifications | FCC Class A, IEEE 587/ANSI C62.4, CUL, UL 1778, CE |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
8 hrs (more time required with extended battery option) |
Visual Indicators | Battery level, Load level, AC in, Inverter on, Summary alarm, Alarm silence, Load on |
---|---|
Switches / Control Panel | System power, Cold start, Load I, Load II, Test, Alarm silence |
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
Intelligent Computer Interfaces | RS232 data interface (DB-9), Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software) |
Contact Closures | DB-9, Open collector |
SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
---|
Model | VA | Watts | Input Current | Output Current | Rating | Backup Time* 100% / 50% Load |
Weight (lb) | Rackmount H x W x D (in) |
---|---|---|---|---|---|---|---|---|
GT 1250 | 1250 | 875 | 8.8 A | 10.4 A | 1250 VA / 875 W | 10.3 minutes / 26.5 minutes | 80 | 14.1 x 6.9 x 21.0 |
GT 1500 | 1500 | 1050 | 10.7 A | 12.5 A | 1500 VA / 1050 W | 8.1 minutes / 19.8 minutes | 80 | 14.1 x 6.9 x 21.0 |
GT 2000 | 2000 | 1400 | 14.3 A | 16.7 A | 2000 VA / 1400 W | 8.1 minutes / 19.8 minutes | 100 | 14.1 x 6.9 x 21.0 |
GT 2400 | 2400 | 1680 | 18.3 A | 20.0 A | 2400 VA / 1680 W | 5.7 minutes / 15.5 minutes | 100 | 14.1 x 6.9 x 21.0 |