Built for extreme temperatures for applications where others have failed
Voltage | 120 VAC +12%, -25% (without battery discharge) |
---|---|
Frequency | 45 Hz to 65 Hz |
Current | 7.2 A |
Voltage | 120 VAC ±3% |
---|---|
Frequency | Software selectable to sync with input utility or run at crystal controlled 50/60 Hz ±1 Hz |
Current | 8.3 A |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | <1% |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | -40°C to +74°C (-40°F to +165°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Noise Level | 46 dBA at 5 ft |
Input | NEMA 5-15P plug with 6 ft cord |
---|---|
Outputs | 5-15R receptacles |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, RS232 data interface, Inverter powers load continuously, Continuous operation on -25% to +12% utility without draining batteries, Automatic bypass, AC output (2 channel load control), Rear mounted ground stud |
---|---|
Certifications | FCC Class A, IEEE 587/ANSI C62.4, IEC 555 @ 120 VA, CUL, UL 1778 |
MTBF | Inverter: > 100,000 hrs |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
8 hrs (more time required with extended battery option) |
Visual Indicators | Battery level, Load level, AC in, Inverter on, Summary alarm, Alarm silence, Load on |
---|---|
Switches / Control Panel | System power, Cold start, Load I, Load II, Test, Alarm silence |
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
Intelligent Computer Interfaces | Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software) |
Contact Closures | Open collector (see user manual for additional interface information) |
SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
---|
Model | VA | Watts | Input Current | Output Current | Rating | Backup Time* 100% / 50% Load |
Weight (lb) | Rackmount H x W x D (in) |
---|---|---|---|---|---|---|---|---|
DT 1000R ET | 1000 | 700 | 7.2 A | 8.3 A | 1000 VA / 700 W | 5.0 minutes / 17.0 minutes | 30 | 3.5 x 19.0 x 18.0 (2U) |
* Backup time is based on 41 Ah batteries