Built for extreme temperatures for applications where others have failed
Voltage | 120 VAC +12%, -25% (without battery discharge) |
---|---|
Frequency | 45 Hz to 65 Hz |
Current | 7.2 A |
Voltage | 120 VAC ±3% |
---|---|
Frequency | Software selectable to sync with input utility or run at crystal controlled 50/60 Hz ±1 Hz |
Current | 8.3 A |
Crest Factor Ratio | 50% load up to 4.8:1, 75% load up to 3.2:1, 100% load up to 2.4:1 |
THD | <1% |
Dynamic Response | ±4% for 100% step load change 0.5 ms recovery time |
Overload | 110% for 10 sec; 200% for 50 ms |
UPS Protection | Input and output short circuit, Input and output overload, Excessive battery discharge |
Temperature | -40°C to +74°C (-40°F to +165°F) |
---|---|
Humidity | 0% to 95% non-condensing |
Altitude | Sea level to 10,000 ft |
Noise Level | 46 dBA at 5 ft |
Input | NEMA 5-15P plug with 6 ft cord |
---|---|
Outputs | 5-15R receptacles |
Weight (lb) | 30 |
Cooling | Low velocity forced air with user-selectable direction of airflow and user-replaceable filters |
Standard Features | Power factor corrected input, Fully regenerative, True on-line continuous power, Low distortion sine wave output, Designed for non-linear loads, Extended brownout protection, RS232 data interface, Inverter powers load continuously, Continuous operation on -25% to +12% utility without draining batteries, Automatic bypass, AC output (2 channel load control), Rear mounted ground stud |
---|---|
Certifications | FCC Class A, IEEE 587/ANSI C62.4, IEC 555 @ 120 VA, CUL, UL 1778 |
Typical Recharge Time (to 85% Capacity @ 100% Load) |
8 hrs (more time required with extended battery option) |
Visual Indicators | Battery level, Load level, AC in, Inverter on, Summary alarm, Alarm silence, Load on |
---|---|
Switches / Control Panel | System power, Cold start, Load I, Load II, Alarm silence, Battery test |
Audible Alarms | Utility interrupt, Inverter failure, Overload, Low battery, Self test |
Intelligent Computer Interfaces | Full interactive remote computer monitoring and control of most features including load control (requires optional monitoring software) |
Contact Closures | Open collector |
SNMP Interface | Allows full control and monitoring interface over network connection. Compatible with HP Openview™, IBM Netview™, CA Unicenter TNG™, and other major software offerings. |
---|
Model | VA | Watts | Input Current | Output Current | Rating | Backup Time* 100% / 50% Load |
Weight (lb) | Rackmount H x W x D (in) |
---|---|---|---|---|---|---|---|---|
DT 1250R | 1250 | 875 | 8.8 A | 10.4 A | 1250 VA / 875 W | 7.0 minutes / 21.0 minutes | 42 | 3.5 x 19.0 x 17.0 (2U) |
DT 1500R | 1500 | 1050 | 10.7 A | 12.5 A | 1500 VA / 1050 W | 5.0 minutes / 17.0 minutes | 42 | 3.5 x 19.0 x 17.0 (2U) |
DT 2000R | 2000 | 1400 | 14.3 A | 16.7 A | 2000 VA / 1400 W | 5.0 minutes / 18.0 minutes | 55 | 3.5 x 19.0 x 17.0 (2U) |
DT 2400R | 2400 | 1680 | 18.0 A | 20.0 A | 2400 VA / 1680 W | 4.5 minutes / 14 minutes | 55 | 3.5 x 19.0 x 17.0 (2U) |
* Backup time is based on 5 Ah batteries